首页 | 官方网站   微博 | 高级检索  
     

高压直流换流站污秽水平预测方法研究
引用本文:宿志一,范建斌,谷琛,周军.高压直流换流站污秽水平预测方法研究[J].中国电机工程学报,2007,27(13):1-5.
作者姓名:宿志一  范建斌  谷琛  周军
作者单位:中国电力科学研究院,北京市,海淀区,100085
基金项目:国家计委高技术产业发展司重点项目
摘    要:对换流站站址周边地区气象、工业污染源和输变电设备运行的相关资料进行收集,根据风洞试验得出的绝缘子表面积污模式,利用污染源扩散模式计算站址及周边地区交流盘形绝缘子积污水平。在此基础上,根据国内已有换流站和自然积污站的直、交流积污数据并结合具体情况,选择合适的直交流积污比,由计算出的交流盘形绝缘子污秽水平估算出换流站直流场设备的污秽水平。根据该污秽水平,计算出换流站直流场支柱绝缘子以及不同管径的套管表面的污秽度。根据标准直流支柱绝缘子的人工污秽试验数据和预估算的污秽度,确定直流支柱绝缘子和各类套管的爬电比距。文中提出的方法可用于±500kV、±800kV高压直流换流站污秽水平预测及外绝缘配置。

关 键 词:高压换流站  大气污染  污秽水平预测
文章编号:0258-8013(2007)13-0001-05
收稿时间:2007-02-16
修稿时间:2007年2月16日

The Research of Pollution Level Prediction Method of HVDC Converter Stations
SU Zhi-yi,FAN Jian-bin,GU Chen,ZHOU Jun.The Research of Pollution Level Prediction Method of HVDC Converter Stations[J].Proceedings of the CSEE,2007,27(13):1-5.
Authors:SU Zhi-yi  FAN Jian-bin  GU Chen  ZHOU Jun
Abstract:Information about meteorological conditions, industry pollution sources and operation conditions of electrical equipment in HVDC converter stations is collected,and based on contamination depositing mode on insulator surface which is acquired by wind tunnel test, the pollution level of AC cap and pin insulator in HVDC converter stations and ambient areas is calculated using diffusion mode of pollution sources. On the basis of AC and DC contamination depositing data of converter stations and natural contamination depositing stations in China, combined with concrete conditions, the appropriate contamination depositing ratio of DC to AC voltage is selected, and the pollution level of devices in DC yard is estimated using calculated pollution level of AC cap and pin insulator. Based on this predicted pollution level, the pollution level of post insulator and bushings with different diameters in DC yard are calculated. Based on artificial pollution test data of standard DC post insulators and predicted pollution level, the specific creepage distance of DC post insulator and different kinds of bushings are determined. The method introduced in this paper can be used to predict pollution level and to select insulation dimensioning of 500kV and 800kV HVDC converter stations.
Keywords:HVDC converter stations  atmosphere pollution  pollution lever forecast
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《中国电机工程学报》浏览原始摘要信息
点击此处可从《中国电机工程学报》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23