首页 | 官方网站   微博 | 高级检索  
     


Approaches for improving airflow uniformity in unidirectional flow cleanrooms
Affiliation:1. Centre for Computational Mechanics, National University of Singapore, Singapore 119260;2. Supersymmetry Services Pte Ltd, Singapore 139952;1. Division of Fluid and Climate Technology, School of Architecture and the Built Environment, KTH Royal Institute of Technology, Stockholm, Sweden;2. Department of Medicine, Solna (MedS), Unit of Infectious Diseases, Karolinska Institutet, Stockholm, Sweden
Abstract:Airflow behavior inside a cleanroom with vertical unidirectional flow has been investigated. The design parameters, such as porosity and height of raised floor, width of cleanroom and inlet velocity profile, which affect the uniformity of air velocity distribution inside the cleanroom have been studied computationally. The Reynolds-averaged Navier–Stokes equations governing the flow are solved using a finite-volume code STAR-CD. The standard k-ε turbulence model has been used. Approaches for improving airflow uniformity have been proposed and quantitatively examined based on intensive case studies. The present results show that the uniformity increases along with the height of raised floor. Alternatively, better airflow uniformity can also be achieved through a proper allocation of floor porosity or by controlling the distribution of inlet velocity profile. Suggestions on how to design unidirectional cleanrooms with desired airflow uniformity under practical constraints have been given.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号