1.
介绍了西门子20Hz电压注入式100%定子接地保护原理,分析了在调试时接地电流角度补偿与传变电阻对西门子20Hz电压注入式100%定子接地保护的影响.通过软件调试,对接地电流角度补偿与传变电阻的修正,提高了20Hz接地保护测量接地电阻的精度,并给出了防止20Hz电源及电源引出线故障误动的措施. 相似文献
2.
3.
4.
为解决接地网及其他谐波对接地网接地电阻测量的影响,提高测量精度,采用正弦脉宽调制SPWM (Sinusoidal Pulse-Width Modulation)、数字频率合成DDFS(Direct Digital Frequency Synthesis)及微处理器控制技术,研制出了多功能接地电阻测量装置.该装置基于变频测量原理控制电源按设定的频率点输出交流信号,并经电流极注入接地网(频率范围30~70 Hz),在对电压极、电流极的测量值进行数字滤波及离散傅里叶变换DFT(Discrete Fourier Transfom)后,依据获得的电压、电流同相分量计算出接地网接地阻抗及阻性分量.型式试验及现场测量结果表明,该装置操作方便、性能稳定,有效地消除了工频干扰以及谐波干扰,测量数据准确可靠,符合<接地装置特性参数测量导则>对接地网接地电阻测量的要求,适合接地网接地阻抗、土壤电阻率、导通电阻的测量. 相似文献
5.
6.
文章介绍应用40/60 Hz电源,滤除地中干扰电流,同时消除了测量导线间互感的影响,实现了小电流测量大型地网接地阻的方法,还介绍了根据这个原理研制的PC-19型大型地网接地电阻测量仪及其应用效果。 相似文献
7.
8.
9.
10.
基于相间电阻变化特征的故障选相元件 总被引:1,自引:1,他引:0
针对现有选相元件在系统振荡期间存在误选相问题,提出了一种基于相间电阻变化特征的高压输电线路故障选相新原理。发生不对称接地故障时,首先利用零序和负序电流之间的相位关系分成3个区域,每个区域存在单相接地和两相短路接地2种故障类型,在判断出某个分区后根据相间测量电阻的变化特征得到选相结果。在系统振荡期间,健全相相间测量电阻是连续缓慢变化的;短路相之间的相间测量电阻,在发生故障瞬间是突变的,而故障后则基本没有变化。仿真结果表明,发生相间故障时,相间测量电阻不受负荷电流、过渡电阻、分支系数和系统振荡等的影响,该选相元件有很高的动作可靠性和准确性,适用于系统振荡期间的选相元件。 相似文献
11.
探讨了一种基于嵌入式系统新型接地网特性测量装置的开发方案,采用变频测量方法,能在30~70Hz频段间1Hz步进,选择最佳测量频率,避开工频环境中的干扰信号,实现接地网特性参数的准确测量。设计的测量装置由变频电源、测量处理模块、嵌入式控制核心组成,其中处理器采用ARM7TDMI内核的32位高速处理器。系统软件包括准同步采样、数字滤波、电参量计算等,由固化在嵌入式ARM芯片中的程序实现。方案充分利用嵌入式技术特点,通过传感器、A/D转换器等较少硬件,完成接地网参数的测量,应用结果证明设计方案高效、可靠,满足测量要求。 相似文献
12.
大电流法与异频法测量地网电阻比较 总被引:1,自引:0,他引:1
杨柳 《广东输电与变电技术》2009,11(5):42-43
传统的50Hz工频大电流法测量接地电阻难于排除干扰,测量工作量大,不易实施。异频法接地电阻测量,能有效地躲过工频干扰,以较小的测量电流,得到比较准确接地电阻测量结果。实践证明,异频法将逐渐代替50Hz工频大电流法,成为测量变电站接地电阻的主要方法。 相似文献
13.
The main problems of tower grounding resistance measurement are the unknown position of the tower grounding body caused by long-time buried span that affects measurement accuracy because of the imprecise electrode arrangement, the low efficiency achieved when measuring without a connected grounding lead, and the large error obtained when a tower grounding lead is connected. Hence, a novel method to measure tower grounding resistance is presented in this paper. In the proposed method, current of different frequency ranges is injected through the grounding lead on the premise of connecting a tower grounding lead. On the one hand, this method detects the buried position by analyzing the surface magnetic field intensity caused by exciting current. On the other hand, the method measures the tower grounding resistance value of different frequency ranges to obtain an accurate value through data processing. A measurement model with a connected grounding lead was constructed. The surface magnetic field distribution of the grounding body was analyzed. The accurate measurement condition was evaluated to determine the frequency range of exciting current and the data processing method. Finally, a simulation was performed to verify the method. Results showed that the method can identify the position of the tower grounding body and can measure the resistance accurately with a connected grounding lead. 相似文献
14.
采用电流-电压三极法测量架空线路杆塔的工频接地电阻时,架空避雷线对注入杆塔地网的测量电流具有分流作用,从而影响接地电阻的测量精度。建立了架空避雷线对注入杆塔地网的测量电流的分流模型,分析了避雷线分流的程度和影响分流效果的因素及其影响规律。结果表明:(1)避雷线分流所占比重可以达到60%以上,当测量杆塔接地电阻较大、非测量杆塔接地电阻较小、测量杆塔为变电站出线上的前2座杆塔时,避雷线分流效果更明显;(2)仅考虑分流电流大小对杆塔接地电阻测量的影响是不够的,忽略分流电流与测量电流的相角差同样会造成较大的测量误差,导致接地电阻的测量值偏高。 相似文献
15.
针对大型接地网接地电阻传统方法测量值分散性大,可信度低的问题,查找出工频干扰电压偏大是影响要数,采用异频测量方法,提高了测量准确性。 相似文献
16.
详细总结分析了接地电阻测量中引起测量异常和测量误差的各种因素 ,得出克服测量异常及减小误差的方法 ,提出构成新接地电阻测量仪的新思路。 相似文献