首页 | 官方网站   微博 | 高级检索  
     

基于膜分离器的NH3-H2O-LiBr吸收式制冷系统的研究分析
引用本文:岳小洋,李舒宏,徐梦凯,李彦军,杜垲,杨柳.基于膜分离器的NH3-H2O-LiBr吸收式制冷系统的研究分析[J].化工进展,2019,38(2):813-818.
作者姓名:岳小洋  李舒宏  徐梦凯  李彦军  杜垲  杨柳
作者单位:东南大学能源与环境学院,江苏南京,210000;东南大学能源与环境学院,江苏南京,210000;东南大学能源与环境学院,江苏南京,210000;东南大学能源与环境学院,江苏南京,210000;东南大学能源与环境学院,江苏南京,210000;东南大学能源与环境学院,江苏南京,210000
基金项目:国家自然科学基金(51476026,51876033);国家十三五重点研发计划子任务(2017YFC0702501-3)
摘    要:氨-水-溴化锂(NH3-H2O-LiBr)三元吸收式制冷系统中溴化锂的存在有利于发生过程的进行,降低循环精馏热,但阻碍了吸收氨的传质过程,对吸收性能不利。对此本文提出基于膜分离器的氨-水-溴化锂吸收式制冷循环,可将溴化锂从进入吸收器的溶液中分离出来,进而改善吸收性能。并进行了在膜分离器中分离溴化锂的实验,实验结果表明NH3-H2O-LiBr三元溶液在膜分离器中两次循环后分离效率达98%。基于实验中的分离效率,利用Aspen Plus模拟器,进一步模拟分析了基于膜分离器的氨-水-溴化锂吸收式制冷系统,并计算其性能系数(COP)。结果表明,与普通三元循环相比,基于膜分离器的新型循环的能耗较低,性能系数可提高近10%。当发生温度从60℃升高到120℃时,循环的发生器热负荷逐渐降低,COP逐渐增大,最大达0.5869,较普通循环高6%,此时溴化锂质量分数变化范围为0~30%。

关 键 词:吸收式制冷  模拟  性能系数  AspenPlus  膜分离器
收稿时间:2017-12-15

Analysis of NH3-H2O-LiBr absorption refrigeration system based on membrane separator
Xiaoyang YUE,Shuhong LI,Mengkai XU,Yanjun LI,Kai DU,Liu YANG.Analysis of NH3-H2O-LiBr absorption refrigeration system based on membrane separator[J].Chemical Industry and Engineering Progress,2019,38(2):813-818.
Authors:Xiaoyang YUE  Shuhong LI  Mengkai XU  Yanjun LI  Kai DU  Liu YANG
Affiliation:School of Energy and Environment, Southeast University, Nanjing 210000, Jiangsu, China
Abstract:The existence of lithium bromide can significantly improve the process of generation and reduce energy consumption of rectification. But it has negative effect on the absorption process of ammonia. Therefore, the new cycle of NH3-H2O-LiBr absorption refrigeration system based on membrane separator was proposed to separate lithium bromide from the solution stream entering absorber and improve absorption performance. And the experiment for separating lithium bromide in the membrane separator was carried out. The results showed that the separation efficiency of lithium bromide can reach 98% after twice solution cycle in membrane separator. Based on the separation efficiency of experiments, the Aspen Plus monitor process was used for further simulating and analyzing the NH3-H2O-LiBr absorption refrigeration system with membrane separator. Simulation results indicated that due to the application of membrane separator, the energy consumption of new cycle based on membrane separator was lower than the normal absorption system and the COP can be improved nearly 10%. When generator temperature increased from 60℃ to 120℃, the generator heat load decreased and the COP of absorption cycle increased with the highest value of 0.5869 at the mass fraction of lithium bromide ranging from 0—30%.
Keywords:absorption refrigeration  simulation  COP  Aspen Plus  membrane separator  
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《化工进展》浏览原始摘要信息
点击此处可从《化工进展》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号